- Welcome to Zhejiang Weihao Electronic Co., Ltd
- Download
- Contact us
- Select Language
At input side, there will be (1/2 ~1 cycle, ex. 1/120 ~ 1/60 seconds for 60 Hz AC source) large pulse current (20~60A based on the design of S.P.S.) at the moment of power on and then back to normal rating. This "Inrush Current" will appear every time you turn on the power. Although it will not damage the power supply, we suggest not turning the power supply ON/OFF very quickly within a short time. Besides, if there are several power supplies turning on at the same time, the dispatching system of AC source may shut off and go into protection mode because of the huge inrush current. It is suggested that these power supplies start up one by one or use the remote control function of S.P.S. to turn them on/off.
Some models control the fan based on internal temperature to extend its life time. For example, the Fan ON temperature for the S-240 series is ≧ 40C (RT1). If the internal temperature does not reach the preset value, the fan will remain still until receiving the start up signal.
b. We also need to consider about ambient temperature of the S.P.S. and whether there is additional device for dissipating the heat. If the S.P.S. is working in a high temperature environment, we need to make some derating to the output power. The derating curve of "ambient temperature" versus "output power" can be found on our spec sheets.
c. Choosing functions based on your application:
1. Protection function: Over Voltage Protection (OVP), Over Temperature Protection (OVP), Over Load Protection (OLP), and etc.PFC stands for Power Factor Correction. The purpose of PFC is to improve the ratio of apparent power and real power. The power factor is only 0.4~0.6 in non-PFC models. In PFC models, the power factor can reach above 0.95. The calculation
formulas are as below:
Apparent Power=Input Voltage x Input Current (VA)
Real Power= Input Voltage x Input Current x Power Factor (W)
From the environment friendly point, the electric power plant needs to generate
a power which is higher than apparent power in order to steadily provide
electricity to the market. The real usage of electricity should be defined by
real power. Assuming the power factor is 0.5, the power plant needs to produce
more than 2VA to satisfy 1W real power. On the contrary, if the power factor is
0.95, the power plant only needs to generate more than 1.06VA to provide 1W
real power need. It will be more effective.
No, you can not do this connection because S-320 is not equipped with the parallel function. When two power supplies are connected in parallel, the one with higher output voltage will share more loading and deliver more (even "all") power to the load and cause these two power supplies to be unbalanced. We suggest using SP-300 or SP-500 because it is equipped with the current sharing function.
Noise is directly related to the fan which is build into the power supply. Lowering the airflow of the fan means reducing the heat dissipation ability. It will also influence the reliability of the products. Furthermore, minimum airflow of fans is defined by Safety Organization and a safety appendage will be needed if using a new fan. Generally, when we choose a suitable power supply, fan is not necessary if wattage is under 200W. Above 240W, a fan is needed.
Ex. In SP-150 derating curve, the ambient temperature difference in application is 5 Celsius from vertical to horizontal. The output wattage in forced cooling can be 20% higher than air cooling convection.
During safety verification process, the agency will use a stricter standard -- ?0%(IEC60950 uses +6%, -10%) of the input voltage range labeled on the power supply to conduct the test. So, operating at the wider input voltage range as specified on the spec. sheet should be fine. The narrower range of input voltage labeled on the power supply is to fulfill the test standard of safety regulation and make sure that users insert input voltage correctly.
We cannot guarantee 100% that the final system can still meet the EMC requirements. The location, wiring and grounding of the switching power supply in the system may influence its EMC characteristics. In different environment or applications, the same switching power supply may have different outcomes. Our test results are based on setup shown in the EMC report.
"Weho Electric allows us to do our jobs better. Without it, we couldn't keep up!"
Better Switching power supply